Sandrine Bailleux | c2f0260 | 2015-12-15 14:27:17 +0000 | [diff] [blame] | 1 | ARM Trusted Firmware Reset Design |
| 2 | ================================= |
| 3 | |
| 4 | 1. [Introduction](#1--introduction) |
| 5 | 2. [General reset code flow](#2--general-reset-code-flow) |
| 6 | 3. [Programmable CPU reset address](#3--programmable-cpu-reset-address) |
| 7 | 4. [Cold boot on a single CPU](#4--cold-boot-on-a-single-cpu) |
| 8 | 5. [Programmable CPU reset address, Cold boot on a single CPU](#5--programmable-cpu-reset-address-cold-boot-on-a-single-cpu) |
| 9 | 6. [Using BL31 entrypoint as the reset address](#6--using-bl31-entrypoint-as-the-reset-address) |
| 10 | |
| 11 | |
| 12 | 1. Introduction |
| 13 | ---------------- |
| 14 | |
| 15 | This document describes the high-level design of the framework to handle CPU |
| 16 | resets in ARM Trusted Firmware. It also describes how the platform integrator |
| 17 | can tailor this code to the system configuration to some extent, resulting in a |
| 18 | simplified and more optimised boot flow. |
| 19 | |
| 20 | This document should be used in conjunction with the [Firmware Design], which |
| 21 | provides greater implementation details around the reset code, specifically |
| 22 | for the cold boot path. |
| 23 | |
| 24 | |
| 25 | 2. General reset code flow |
| 26 | --------------------------- |
| 27 | |
| 28 | The ARM Trusted Firmware (TF) reset code is implemented in BL1 by default. The |
| 29 | following high-level diagram illustrates this: |
| 30 | |
| 31 |  |
| 32 | |
| 33 | This diagram shows the default, unoptimised reset flow. Depending on the system |
| 34 | configuration, some of these steps might be unnecessary. The following sections |
| 35 | guide the platform integrator by indicating which build options exclude which |
| 36 | steps, depending on the capability of the platform. |
| 37 | |
| 38 | Note: If BL31 is used as the Trusted Firmware entry point instead of BL1, the |
| 39 | diagram above is still relevant, as all these operations will occur in BL31 in |
| 40 | this case. Please refer to section 6 "Using BL31 entrypoint as the reset |
| 41 | address" for more information. |
| 42 | |
| 43 | |
| 44 | 3. Programmable CPU reset address |
| 45 | ---------------------------------- |
| 46 | |
| 47 | By default, the TF assumes that the CPU reset address is not programmable. |
| 48 | Therefore, all CPUs start at the same address (typically address 0) whenever |
| 49 | they reset. Further logic is then required to identify whether it is a cold or |
| 50 | warm boot to direct CPUs to the right execution path. |
| 51 | |
| 52 | If the reset vector address (reflected in the reset vector base address register |
| 53 | `RVBAR_EL3`) is programmable then it is possible to make each CPU start directly |
| 54 | at the right address, both on a cold and warm reset. Therefore, the boot type |
| 55 | detection can be skipped, resulting in the following boot flow: |
| 56 | |
| 57 |  |
| 59 | |
| 60 | To enable this boot flow, compile the TF with `PROGRAMMABLE_RESET_ADDRESS=1`. |
| 61 | This option only affects the TF reset image, which is BL1 by default or BL31 if |
| 62 | `RESET_TO_BL31=1`. |
| 63 | |
| 64 | On both the FVP and Juno platforms, the reset vector address is not programmable |
| 65 | so both ports use `PROGRAMMABLE_RESET_ADDRESS=0`. |
| 66 | |
| 67 | |
| 68 | 4. Cold boot on a single CPU |
| 69 | ----------------------------- |
| 70 | |
| 71 | By default, the TF assumes that several CPUs may be released out of reset. |
| 72 | Therefore, the cold boot code has to arbitrate access to hardware resources |
| 73 | shared amongst CPUs. This is done by nominating one of the CPUs as the primary, |
| 74 | which is responsible for initialising shared hardware and coordinating the boot |
| 75 | flow with the other CPUs. |
| 76 | |
| 77 | If the platform guarantees that only a single CPU will ever be brought up then |
| 78 | no arbitration is required. The notion of primary/secondary CPU itself no longer |
| 79 | applies. This results in the following boot flow: |
| 80 | |
| 81 |  |
| 83 | |
| 84 | To enable this boot flow, compile the TF with `COLD_BOOT_SINGLE_CPU=1`. This |
| 85 | option only affects the TF reset image, which is BL1 by default or BL31 if |
| 86 | `RESET_TO_BL31=1`. |
| 87 | |
| 88 | On both the FVP and Juno platforms, although only one core is powered up by |
| 89 | default, there are platform-specific ways to release any number of cores out of |
| 90 | reset. Therefore, both platform ports use `COLD_BOOT_SINGLE_CPU=0`. |
| 91 | |
| 92 | |
| 93 | 5. Programmable CPU reset address, Cold boot on a single CPU |
| 94 | ------------------------------------------------------------- |
| 95 | |
| 96 | It is obviously possible to combine both optimisations on platforms that have |
| 97 | a programmable CPU reset address and which release a single CPU out of reset. |
| 98 | This results in the following boot flow: |
| 99 | |
| 100 |  |
| 102 | |
| 103 | To enable this boot flow, compile the TF with both `COLD_BOOT_SINGLE_CPU=1` |
| 104 | and `PROGRAMMABLE_RESET_ADDRESS=1`. These options only affect the TF reset |
| 105 | image, which is BL1 by default or BL31 if `RESET_TO_BL31=1`. |
| 106 | |
| 107 | |
| 108 | 6. Using BL31 entrypoint as the reset address |
| 109 | ---------------------------------------------- |
| 110 | |
| 111 | On some platforms the runtime firmware (BL3x images) for the application |
| 112 | processors are loaded by some firmware running on a secure system processor |
| 113 | on the SoC, rather than by BL1 and BL2 running on the primary application |
| 114 | processor. For this type of SoC it is desirable for the application processor |
| 115 | to always reset to BL31 which eliminates the need for BL1 and BL2. |
| 116 | |
| 117 | TF provides a build-time option `RESET_TO_BL31` that includes some additional |
| 118 | logic in the BL31 entry point to support this use case. |
| 119 | |
| 120 | In this configuration, the platform's Trusted Boot Firmware must ensure that |
| 121 | BL31 is loaded to its runtime address, which must match the CPU's `RVBAR_EL3` |
| 122 | reset vector base address, before the application processor is powered on. |
| 123 | Additionally, platform software is responsible for loading the other BL3x images |
| 124 | required and providing entry point information for them to BL31. Loading these |
| 125 | images might be done by the Trusted Boot Firmware or by platform code in BL31. |
| 126 | |
| 127 | Although the ARM FVP platform does not support programming the reset base |
| 128 | address dynamically at run-time, it is possible to set the initial value of the |
| 129 | `RVBAR_EL3` register at start-up. This feature is provided on the Base FVP only. |
| 130 | It allows the ARM FVP port to support the `RESET_TO_BL31` configuration, in |
| 131 | which case the `bl31.bin` image must be loaded to its run address in Trusted |
| 132 | SRAM and all CPU reset vectors be changed from the default `0x0` to this run |
| 133 | address. See the [User Guide] for details of running the FVP models in this way. |
| 134 | |
| 135 | Although technically it would be possible to program the reset base address with |
| 136 | the right support in the SCP firmware, this is currently not implemented so the |
| 137 | Juno port doesn't support the `RESET_TO_BL31` configuration. |
| 138 | |
| 139 | The `RESET_TO_BL31` configuration requires some additions and changes in the |
| 140 | BL31 functionality: |
| 141 | |
| 142 | #### Determination of boot path |
| 143 | |
| 144 | In this configuration, BL31 uses the same reset framework and code as the one |
| 145 | described for BL1 above. Therefore, it is affected by the |
| 146 | `PROGRAMMABLE_RESET_ADDRESS` and `COLD_BOOT_SINGLE_CPU` build options in the |
| 147 | same way. |
| 148 | |
| 149 | In the default, unoptimised BL31 reset flow, on a warm boot a CPU is directed |
| 150 | to the PSCI implementation via a platform defined mechanism. On a cold boot, |
| 151 | the platform must place any secondary CPUs into a safe state while the primary |
| 152 | CPU executes a modified BL31 initialization, as described below. |
| 153 | |
| 154 | #### Platform initialization |
| 155 | |
| 156 | In this configuration, when the CPU resets to BL31 there are no parameters that |
| 157 | can be passed in registers by previous boot stages. Instead, the platform code |
| 158 | in BL31 needs to know, or be able to determine, the location of the BL32 (if |
| 159 | required) and BL33 images and provide this information in response to the |
| 160 | `bl31_plat_get_next_image_ep_info()` function. |
| 161 | |
| 162 | Additionally, platform software is responsible for carrying out any security |
| 163 | initialisation, for example programming a TrustZone address space controller. |
| 164 | This might be done by the Trusted Boot Firmware or by platform code in BL31. |
| 165 | |
| 166 | - - - - - - - - - - - - - - - - - - - - - - - - - - |
| 167 | |
| 168 | _Copyright (c) 2015, ARM Limited and Contributors. All rights reserved._ |
| 169 | |
| 170 | |
| 171 | [User Guide]: user-guide.md |
| 172 | [Firmware Design]: firmware-design.md |